Heat pump size calculator

The calculator needs JavaScript. The worked example, formula and figures below show exactly how it works, so you can do the sum yourself. A guide, not advice. Check your supplier's or maker's figures before ordering.

Short answer

Worked example

Worked example inputs
You enterValue
Heat loss of the house at the design temperature6,000 W
Flow temperature45 °C
Return temperature40 °C
Radiator exponent n1.3
Existing radiatorsLiving room: room heat loss 1,000 W, room temperature 21 °C, radiator output at δt50 2,000 W

Heat pump: at least 6.0 kW at your design conditions

Worked example results
ResultValue
Heat pump output needed at design conditions6 kW (20,473 BTU/h)
For heating6 kW
For hot water0 kW
Radiators to upgrade1
Radiators at this flow temperature
RoomHeat lossRadiator gives
Living room1,000 W668 WUpgrade
Show the working
  1. Heating: 6,000 W ÷ 1,000 = 6 kW
  2. Required at design conditions: 6 kW (no margin added)
  3. Living room: ΔT 21.5 K, 2,000 W × 0.334 = 668 W vs 1,000 W heat loss

How it works

  1. Required output (kW) = (heat loss at the design outdoor temperature + hot water allowance) ÷ 1000, with no extra margin added
  2. Compare it with the maker's output at your design outdoor and flow temperatures, not the headline rating
  3. Each radiator gives its ΔT50 output × (ΔT ÷ 50)^n, where ΔT = (flow + return) ÷ 2 − room temperature

An MCS installer sizes the heat pump from their own room-by-room heat loss (MCS MIS 3005-D). This is a planning guide.

Heat pump output falls as the outdoor temperature drops: use the maker's figure at your design outdoor and flow temperatures.

A heat pump needs its own circuit: check your supply's maximum demand with an electrician.

Our default (adjustable)

These are typical planning figures and our own allowances, not facts about your product. Change any of them in the calculator to match your bag, pack or tin.

FigureOur default (adjustable)KindSource
Radiator exponent n1.3 Our assumption
Not yet checked against the source
Our choice: change it to suit your job
Radiator exponent n, default 1.3 as stated in brief v2 H2 ("typical from makers"). Stored as an assumption until the Researcher cites a maker's data sheet (e.g. Stelrad, Zehnder) and switches it to typical.

Regulations and standards

  • MCS MIS 3005-D (heat pump design and sizing; Researcher to confirm the clause)
  • BS EN 12831-1 (heat loss)

Explained: MCS MIS 3005-D (heat pump design), BS EN 12831 and CIBSE DHDG (heat loss).

Our checks use the guidance for England unless a badge says otherwise. Wales, Scotland and Northern Ireland have their own rules: check the source for where you live.